Predesign
___
All required deliverables submitted.
___
Consistent with DSC Sustainability Design Standards.
___
Class C cost estimate accurate and correct for major sustainability and energy features (e.g. turbines, photovoltaic (PV), geothermal wells, solar hot water, etc.).
___
For building project, review building orientation and siting impact on sustainability and energy usage.
___
If available, EUI (energy utilization index) or anticipated energy performance is appropriate for the building type, location and anticipated usage.
___
NPS Project Sustainability Checklist submitted with Predesign (PD) portion completed and an Integrated Design Narrative has been completed.
Schematic Design
___
All required deliverables submitted.
___
Consistent with DSC Sustainability Design Standards
___
Mechanical, plumbing, irrigation and electrical systems (including lighting) are selected to achieve projects energy performance and water efficiency goals / Federal requirements.
___
Architectural design incorporates appropriate wall types, roof types, glazing, moisture protection and insulation U/R (thermal conductivity resistance) values for space use and climate zone.
___
Energy analysis and life cycle analysis for mechanical, electrical, and energy systems selection accurate and correct and includes NPS input on occupancy schedules.
___
Design narrative includes descriptions of all proposed sustainability and energy related features as well as architectural, mechanical, plumbing, irrigation and electrical systems (including lighting).
___
Class B estimate accurate and correct for major sustainability and energy features (e.g. turbines, PV, geothermal wells, solar hot water, etc.).
___
NPS Project Sustainability Checklist submitted with Schematic Design (SD) portion completed.
___
For renewable energy systems, instruct Architect/Engineer (AE) Team of potential grid tied issues.
Design Development (DBB or DB)
___
All required deliverables submitted.
___
Consistent with DSC Sustainability Design Standards.
___
Architectural design incorporates appropriate wall types, roof types, glazing, moisture protection and insulation U/R values for space use and climate zone.
___
Outline specifications for all proposed mechanical, electrical, plumbing and energy systems. Items related to LEED™ (Leadership in Energy and Environmental Design) or Federal Sustainability requirements have been included in the appropriate sections.
___
Heating and cooling load calculations accurate and correct.
___
Lighting power density calculations accurate and correct.
___
Energy analysis and life cycle analysis for mechanical, electrical, and energy systems selection accurate and correct. ASHRAE (American Society of Heating, Refrigerating and Air Conditioning) Advanced Energy Design Guide may be used in lieu of computer simulated energy analysis.
___
Plumbing fixture and irrigation water efficiency calculations accurate and correct.
___
Revised Class B estimate accurate and correct for major sustainability and energy features (e.g. turbines, PV, geothermal wells).
___
All energy systems equipment (PV, inverters, hydro electric turbines, solar hot water, etc.) are rated for the locations in which they are installed.
___
LEED Credit Support Information if project is pursuing formal/informal certification (material or equipment product files, LEED Scorecard, LEED specific drawings, etc.)
___
Any items not available or provided at DD phase will be reviewed in 100% Draft Construction Documents (CD) phase.
100% Draft Construction Documents (DBB) or 100% Draft Design-Build Construction Documents (DB)
General
___
All required deliverables submitted.
___
Consistent with DSC Sustainability Design Standards.
___
All required specification sections provided. Cx Specification includes the appropriate systems and equipment to be commissioned.
___
Equipment and materials conform to NPS standards.
___
All energy system components/equipment has adequate service clearance.
___
Specifications thoroughly coordinated with drawings and product files.
___
Class A estimate accurate and correct for major sustainability and energy features (i.e turbines, PV, geothermal wells).
___
LEED Credit Support Info if project is pursuing formal/informal certification (material or equipment product files, LEED Scorecard, LEED specific drawings, etc.).
Heating, Venitalation, and Air Conditioning (HVAC)
___
HVAC systems designed to conform to all applicable energy codes and standards.
___
Ventilation air provided per ASHRAE 62.
___
Thermal comfort provided per ASHRAE 55.
___
Overall general review of HVAC systems, design and equipment selection.
Plumbing
___
Plumbing systems designed to conform to all applicable codes and standards.
___
Low-flow fixtures and fittings specified.
___
Water bottle filling station integrated into drinking fountain units.
___
Overall general review of plumbing systems, design, and equipment selection.
Electrical
___
Exterior light fixtures are IES (Illuminating Engineering Society) Full Cut-Off.
___
Interior light power density and lighting type(s) is appropriate.
Architecture
___
Thermal breaks included at fenestration; manufactured components and custom installations.
___
Thermal barriers included at rim joists, and at exposed foundations (between ground line and insulated exterior wall systems).
___
Perimeter insulation is continuous along foundation extending to sub-grade.
___
Dew point locations in walls, roofs, and terraces have been determined, and vapor retarders have been provided where required.
___
Sustainable design principles, framing techniques, materials, etc. have been incorporated into the design to the greatest extent technically feasible and within budget.
100% Complete Construction Documents (DBB) or 100% Complete Design-Build Construction Documents (DB)
___
All required deliverables submitted.
___
All review comments from 100% Draft Review satisfactorily resolved.